SMART-UPS 1400VA RM EXT RUN BLACK
Smart-ups 1400va Rackmount Extended Run(3U) Black Option : Extended Battery - SU24R2XLBP EQUIPMENT PROTECTION POLICY - $300K
RACK HEIGHT: 3 U; COLOR: BLACK; UNITS PER PALLET: 12 PI DATE: Oct 2004
OUTPUT POWER CAPACITY: 1,400 VA; OUTPUT POWER CAPACITY: 1,050 Watts
MAX CONFIGURABLE POWER: 1,400 VA; MAX CONFIGURABLE POWER: 1,050 Watts
NOMINAL OUTPUT VOLT: 230 V; OUTPUT VOLT DISTORTION: < 5% at full load
OUTPUT FREQUENCY (sync to mains): 47-53Hz for 50Hz nominal,
57-63Hz for 60Hz nominal
CREST FACTOR: up to 5 : 1; Waveform type: Sinewave
OUTPUT CONNECTIONS: (8) IEC 320 C13; (3) IEC Jumpers
NOMINAL INPUT VOLTAGE: 230V
INPUT FREQUENCY: 50/60 Hz +/- 3 Hz (auto sensing)
INPUT CONNECTION TYPE: IEC-320 C14; CORD LENGTH: 6 feet
INPUT VOLTAGE RANGE FOR MAIN OPERATIONS: 176 - 282 V
INPUT VOLTAGE ADJUSTABLE RANGE FOR MAINS OPERATION: 168 - 302 V
POWER: Maint-free sealed Lead-Acid batt-suspended electrolyte : leakproof
REPLACEMENT BATTERY CARTRIDGE: RBC25; RBC QUANTITY: 1
REPLACEMENT BATTERY CARTRIDGE: NOTE UPS and XL Battery Pack use
different RBC. SU24RMXLBP2U uses RBC26.
TYP BACKUP TIME: AT HALF LOAD: 23.4 min(525W); AT FULL LOAD: 6.6min(1050W)
EXTENDED RUN OPTIONS: APC Smart-UPS XL 1400VA RM 3U 230V - Black
INTERFACE PORT: DB-9 RS-232; AVAILABLE SMART SLOT INTERFACE QUANTITY: 1
CONTROL PANEL: LED status display with load and battery bar-graphs and
On Line : On Battery : Replace Battery : and Overload Indicators
FILTERING: Full time multi-pole noise filtering: 0.3% IEEE surge let-thro
: zero clamping response time : meets UL 1449
MAXIMUM DIMENSIONS: (H x W x D)(cm): 13 x 43 x 39; WEIGHT: 32Kgs